September 2011
News Release
AutomatedBuildings.com

BTL Mark: Resolve interoperability issues & increase buyer confidence
BACnet Testing Laboratories

(Click Message to Learn More)



 


Alternative to ASHRAE Standard 62.1 Ventilation Rate Procedure Proposed

Articles
Interviews
Releases
New Products
Reviews
Secured by Cimetrics
Editorial
Events
Sponsors
Site Search
Newsletters
Control Solutions, Inc
Archives
Past Issues
Home
Editors
eDucation
Securing Buildings News
Training
Links
Software
Subscribe
ABB

ATLANTA – Public comment is being sought on the proposed allowance of an additional default value to the ventilation rate procedure in ASHRAE’s indoor air quality standard.

ANSI/ASHRAE Standard 62.1-2010, Ventilation for Acceptable Indoor Air Quality, sets minimum ventilation rates and other requirements for commercial and institutional buildings.  The ventilation rate procedure provides a prescriptive method for determining minimum ventilation requirements. It accounts for pollutant sources from both the building and its occupants, and allows the designer to account for the efficiency of different ventilation systems when delivering outdoor air to the breathing zone.

Some users of Standard 62.1 believe that the ventilation rate procedure is “too complicated,” according to Standard 62.1 chair Roger Hedrick. “While the 62.1 committee disagrees with this in most cases – the basics of the VRP are quite straightforward – the committee agrees that application of the multiple-zone recirculating system equations described in Section 6.2.5 and Appendix A can be complex.”

Proposed addendum f, open for public review until Oct. 16, provides an additional default value for Vpz. 

"Difficulty determining an appropriate value for Vpz seems to be a frequent issue with users of the multiple space equations,” he said. “The committee decided that supplying a default value would simplify application.  However, the default value is necessarily conservative.  In a large number of applications, determining the 'lowest zone primary airflow value expected at the design condition analyzed' will result in a value for Vpz that is higher than the default, resulting in a reduced outdoor air intake requirement."      

Addendum f is open for public review until Oct. 16, 2011, along with proposed addendum h. Also, proposed addendum g to the standard is open for public review until Oct. 31, 2011. For more information, visit www.ashrae.org/publicreviews. The other addenda open for public review are:

•    Addendum h (until Oct. 16). Table 6.1 in the standard includes ventilation rates for “Sports arena (play area)” and “Gym, stadium (play area).”  Both space types have ventilation rates based on floor area only, with a per person rate of zero.  Users of the standard have expressed interest in applying demand controlled ventilation to these space types, which is effectively prohibited by the lack of a per person component to the ventilation rate.  This proposed addendum replaces both of these space types with “Gym, Sports Arena (play area),” with Rp = 20 cfm/person and Ra = 0.06 cfm/ft².  In most cases, the overall ventilation rate for these spaces is expected to decrease, possibly significantly, according to Hedrick.

One concern about allowing CO2-based demand controlled ventilation in these spaces is that the volume per person in these spaces is typically large, which means that CO2 concentration changes will have longer than usual lag times behind occupancy changes, he noted. 

•    Addendum g (open until Oct. 31).  Currently users are directed that for space types that are not listed in Table 6-1 they should select the space type from the table that is most similar to the space being designed.  However, some space types are actually ventilated using the exhaust ventilation requirements of Section 6.5 and Table 6-4.  This proposed addendum adds language directing the user to select the space type that is most similar to the space in question from either Table 6-1 or 6-4, and to design the ventilation for the space according to the Section 6.2 or 6.5, as appropriate

ASHRAE, founded in 1894, is an international organization of some 50,000 persons. ASHRAE fulfills its mission of advancing heating, ventilating, air conditioning and refrigerating to serve humanity and promote a sustainable world through research, standards writing, publishing and continuing education.  For more informationn about ASHRAE visit http://www.ashrae.org.

                                              






footer


OAP
[Click Banner To Learn More]

[Home Page]  [The Automator]  [About]  [Subscribe ]  [Contact Us]

Events

Want Ads

Our Sponsors

Resources